Carlyle 06DR013

06DE

Carrier's compressor line — commercial HVAC and refrigeration applications with North American heritage.

Carlyle logo

Specifications

  • Compression technology: Reciprocating
  • Configuration: Single
  • Enclosure / drive: Semi-Hermetic
  • Variable speed: Fixed-Speed
  • Hazardous-area certification: No
  • Product category: compressor

Qualified refrigerants & capacity

Calculated cooling capacity (kW). The evaporating / condensing temperature each column was evaluated at is listed per refrigerant, because the grid differs by refrigerant.

RefrigerantULTLTMTHTConditions
R134a5.16.72ULT -60 / 45 °C; LT -35 / 45 °C; MT -10 / 45 °C; HT -5 / 45 °C
R404A2.3710.7513.54ULT -60 / 45 °C; LT -35 / 45 °C; MT -10 / 45 °C; HT -5 / 45 °C
R407A2.12ULT -60 / 45 °C; LT -35 / 45 °C; MT -10 / 45 °C; HT -5 / 45 °C
R407F2.23ULT -60 / 45 °C; LT -35 / 45 °C; MT -10 / 45 °C; HT -5 / 45 °C
R448A1.75ULT -60 / 45 °C; LT -35 / 45 °C; MT -10 / 45 °C; HT -5 / 45 °C
R449A1.7ULT -60 / 45 °C; LT -35 / 45 °C; MT -10 / 45 °C; HT -5 / 45 °C
R507A2.3710.8413.66ULT -60 / 45 °C; LT -35 / 45 °C; MT -10 / 45 °C; HT -5 / 45 °C
R513A5.47.12ULT -60 / 45 °C; LT -35 / 45 °C; MT -10 / 45 °C; HT -5 / 45 °C

Related Carlyle models

Frequently asked questions

What refrigerants does the Carlyle 06DR013 support?

The Carlyle 06DR013 is qualified for R134a, R404A, R407A, R407F, R448A, R449A, R507A, R513A. The table above lists capacity at ultra-low, low, medium and high temperature duty for each refrigerant, with the evaporating and condensing temperature each value was calculated at. Those conditions differ by refrigerant, so read them per row.

What is the cooling capacity of the Carlyle 06DR013?

Running on R507A, the Carlyle 06DR013 delivers 2.37 kW at LT (-35 / 45 °C), 10.84 kW at MT (-10 / 45 °C), 13.66 kW at HT (-5 / 45 °C). These are calculated cooling capacities at the rating basis the manufacturer declares with its data, not measured values. Use the Benchmark tool to evaluate capacity at your exact SST/SDT and superheat conditions.

What type of compressor is the Carlyle 06DR013?

DigiEntropy classifies the Carlyle 06DR013 as 06DE. Browse the Carlyle catalog to compare nearby models from the same brand.

Can the Carlyle 06DR013 be retrofit to a lower-GWP refrigerant under EU F-Gas Regulation 2024/573?

Open the F-Gas Retrofit tool with this model pre-selected to see drop-in alternatives ranked by capacity match, COP, GWP, PFAS impact, and 2026/2030/2035 phase-out timeline.

Where does the Carlyle 06DR013 performance data come from?

From Carlyle's own published performance data, evaluated at the suction and liquid conditions the manufacturer declares with it. Which rating standard the manufacturer certifies to (EN 12900 or AHRI 540) is not stated on this page; check the manufacturer's datasheet. Fit your own data in the Polynomial Fitter tool.